Skip to main content

Energia Power

Power Quality Analyser

LDVRC is used to compensate the voltage disturbance that is relatively long time and shallow amplitude. When the protected equipment need a very stable voltage(≤5% of rating voltage), LDVRC is applicable. LDVRC is proposed to be used to solve the problems of short time voltage disturbance and deep sag.

Dynamic Voltage Restorer (DVR)

LDVR Dynamic Voltage Restorer
(DVR WITH ENERGY STORAGE )

Electrical parameters
Rated voltage (line) 0.2kV/0.4kV/0.69kV/6kV/12kV/24kV
Frequency 50Hz/60Hz
Technical Parameters
Response time < 1ms
Compensation range 0~130%*Un/3P
Rated compensation time 500ms~1min (selectable)
500ms~1min (option); longer time can be customized
Voltage unbalance <3%
Frequency tracking error < ±0.1HZ
Output voltage harmonic <2%
Operation Loss <1%
Voltage compensation error <1%
Voltage loss <1%

LDVR Dynamic Voltage Restorer
(DVR WITHOUT ENERGY STORAGE )

Electrical parameters
Rated voltage (line) 0.2kV/0.4kV/0.69kV/6kV/12kV/24kV
Frequency 50Hz/60Hz
Technical Parameters
Response time < 3ms
Compensation range
Input voltage
IN
DVR Input voltage
OUT
Time of duration
3P  50%*Un 100% 30s
2P  40%*Un 100% 30s
1P  30%*Un 95% 30s
1P  0%*Un 1P 60%*Un
2P 90%*Un
30s
3P
(80%~120%6)*Un
100% Continuously
Voltage unbalance <3%
Frequency tracking error < ±0.2HZ
Output voltage harmonic <2.5%
Operation Loss <2%
Voltage compensation error <1%
Voltage loss <2%