Hoko HKE-96 Multi-Function Meter Energy Accuracy Class is 0.5s. The HKE-96 series power meters are easy to use, cost effective and offer the basic measurement capabilities required to monitor electrical installation.

Electrical Characteristics
Type of Measurement True RMS up to 31st harmonics
Measurement Accuracy Voltage, Current, Frequency — Class 0.2
Active Power, Power Factor, Demand — Class 0.5
Active Energy (kWh) — Class 0.5s
Input Voltage Characteristics Inputs — UA, UB, UC, UN
Measured Voltage — 63.5 / 110 / 240 / 415 V AC
Permissible Overload — 1.2 × UN (continuous); 2 × rated value over 1 second
Frequency Range — 45–65 Hz
Burden — Less than 0.5 VA (per phase)
Input Current Characteristics CT Ratings — Primary: 1A–9999A; Secondary: 1A / 5A
Permissible Overload — 1.2 × (continuous); 10 × rated value over 1 second
Burden — Less than 0.5 VA (per phase)
Maximum Demand Yes (Real-Time / Month / Historical)
Energy Pulse Output Optocoupler pulse with open collector
Energy Metering Bi-directional Energy — Yes
Tariff Energy — Yes
Four-quadrant Power — Yes
Power Supply
AC / DC 85V – 265V
Power Consumption Less than 5VA
Product Functions
Voltage Measurement (V)Yes
Current Measurement (A)Yes
Active Power Measurement (kW)Yes
Active Energy Measurement (kWh)Yes
Power Factor Measurement (PF)Yes
Harmonics Measurement (THD)Yes
Maximum Demand (MD)Yes
Display & Operation
Display TypeLCD
Display Background ColourWhite
Meter Temperature DisplayYes
Display LanguageEnglish
Number of Keys4
Communication
RS-485 PortYes
Modbus RTU ProtocolYes
Connections
Type of Electrical Connection Measurement Inputs (Voltage) — Plug-in Type Terminal Blocks
Measurement Inputs (Current) — Screw-type Terminal Blocks
Mechanical Characteristics
Dimensions96 × 96 mm (Flush Mount)
Depth55 mm
Installation Depth42 mm
Cutout91 × 91 mm
Weight350 g
IP Degree of ProtectionFront: IP51; Back: IP30
Environmental Conditions
Operating Temperature-20°C to 70°C
Storage Temperature-40°C to +85°C
Humidity Rating5–95% Non-condensing
AltitudeLess than 2500 m
Safety & Standards
Power Frequency Withstand Voltage (AC 2kV / 1 min)Between auxiliary power supply, voltage signal and current signal
Power Frequency Withstand Voltage (AC 1kV / 1 min)Between switch input, pulse output and communication
Insulation ResistanceInput and output end to chassis more than 100MΩ
ApplicationIndoor installation in stationary panels
Electromagnetic Compatibility
Immunity to Electromagnetic RF FieldsIEC 61000-4-2
Immunity to Conducted DisturbanceIEC 61000-4-6

PD866EY Dot Matrix Network Power Meter

The PD866EY Dot Matrix English Network Power Meter features a large-screen dot matrix display. It utilizes a 96mm outer frame and a very short depth, making it particularly suitable for applications in confined installation spaces. The industrial-standard wide-temperature LCD screen offers excellent performance across a wide temperature range.

Parameter Performance Indicators
Input Signal Network Signal
Three-phase three-wire, three-phase four-wire (refer to wiring diagram)

Frequency
45–65Hz

Voltage
AC: 57.7/100V, 230/415V
Overload: 1.2 × rated value (continuous); 2 × rated value for 1 second
Power Consumption: < 0.5VA per channel

Current
AC: 1A, 5A
Overload: 1.2 × rated value (continuous); 10 × rated value for 1 second
Power Consumption: < 0.5VA per channel
Accuracy Voltage, Current, Power
0.2 class

Active Energy
0.5s class

Reactive Energy
2 class
Power Supply Operating Range: AC/DC 85V–265V
Power Consumption: Main unit ≤ 5VA
Relay Output Contact Type: Normally open (level output or momentary mode)
Contact Capacity: AC 250V/3A, DC 30V/3A
Energy Pulse Output Output Method: Open-collector optocoupler pulse
Transmitter Output Output Type: 4–20mA (load resistance ≤ 350Ω)
Digital Input Supports dry contact input with built-in DC12V power supply
Communication RS485 Modbus-RTU or Ethernet Port Version (Modbus TCP/IP)
Safety Power Frequency Withstand Voltage
Power supply, voltage signal, and current signal withstand voltage: AC 2kV/1min;
Digital input, pulse output, and communication withstand voltage: AC 1kV/1min

Insulation Resistance
Input and output terminals to the case >100MΩ
Electromagnetic Compatibility Level Complies with IEC 61000 standard (Level 4)
Protection Level IP51 (front panel), IP30 (cabinet body, excluding terminals)
Operating Environment Operating Temperature: Instrument: −25°C to +70°C; Display: −20°C to +70°C
Storage Temperature: −40°C to +85°C
Relative Humidity: ≤95% non-condensing
Altitude: ≤2500m